Wiring Of Outputs Of The F-Switch Profisafe Electronic Module - Siemens SIMATIC Operating Instructions Manual

Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

8.3.9

Wiring of Outputs of the F-Switch PROFIsafe Electronic Module

Assignment of Channels
DO0
DO1
DO2
A list of the modules operated behind the F-Switch can be obtained on the Internet under ID
25371449.
Actuator Interconnection
The actuators are interconnected via the power bus.
The PP-switching outputs of the F-Switch PROFIsafe are fed to the actuators via the power
bus. The power bus is permanently wired within the system. As a result, only limited wiring
variations are possible. The power buses can be tapped and routed or conditioned only from
modules of the ET 200pro system.
Wiring Diagram of Frequency Converter (SIL2/Category 3)
Figure 8-33
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
Channel
Wiring Diagram of F-Switch PROFIsafe - Connection of Frequency Converter
Fail-Safe Electronic Modules
8.3 F -Switch PROFIsafe Digital Electronic Module
F0
F1
2L+
Power bus
129