System overview
2.10 System data
Ambient conditions
Ambient temperature
Relative humidity
(non-condensing)
corresponds to class
Installation altitude
Deviations from the specified class are shown in
2)
Mechanical stability
Vibrational load
- Displacement
- Acceleration
- Corresponds to class
Shock load
- Acceleration
- Corresponds to class
Deviations from the specified class are shown in
3)
Note
The relevant weight of a cabinet unit is specified on the test certificate supplied and on the
rating plate. The specified weight corresponds to the actual expansion stage of the cabinet
unit.
34
In operation
0 °C
... +40 °C
2)
to +50 °C see derating data
95 %
5 % ...
2)
3K3 to IEC 60 721-3-3
Cabinet Modules:
up to 2000 m above sea level - no derating,
> 2000 m - see characteristics/derating data
Motor Modules, Booksize Cabinet Kit format:
up to 1000 m above sea level - no derating,
> 1000 m - see characteristics/derating data
italics
.
In operation
0.075 mm at 10 ... 58 Hz
9.8 m/s² at >58 ... 200 Hz
-
100 m/s
for 11 ms
2
3M4 to IEC 60721-3-3
italics
.
During storage
-25 °C to +55 °C
5 %
... 95 %
2)
2)
1K4 to IEC 60 721-3-1
During storage
5 Hz
1.5 mm at
... 9 Hz
3)
5 m/s² at > 9 ... 200 Hz
1M2 to IEC 60721-3-1
40 m/s
for 22 ms
2
1M2 to IEC 60721-3-1
Manual, (GH5), 05/2010, A5E03263538A
During transport
-25 °C to +70 °C
-40 °C
from
for 24 hours
2)
5 % ... 95 % at 40 °C
2K3 to IEC 60 721-3-2
During transport
5 Hz
3.1 mm at
... 9 Hz
3)
10 m/s² at > 9 ... 200 Hz
2M2 to IEC 60721-3-2
100 m/s
for 11 ms
2
2M2 to IEC 60721-3-2