Derating Data - Siemens SINAMICS S120 Manual

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
5.7 Central Braking Modules
Order no.
Weight, approx. (standard version)
Frame size
Power demand of fans.
1)
The specified power loss equals the maximum value at 100 % capacity utilization. The value in normal operation is
2)
lower.
The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43 and IP54
3)
degrees of protection.
Duty cycle
P
Figure 5-38
5.7.6

Derating data

The units have an integrated temperature monitoring function. A fan included as standard
supports the power unit cooling. The fan is switched on and off by means of a temperature
control, which prevents it from running unnecessarily. The permissible ambient temperature
is from 0 °C to 40 °C. For temperatures between 40 °C and 50 °C, the power must be
reduced according to the following formula:
● P = [1 − 0.025 x (T − 40 °C)] x P
The installation altitude above sea level can be up to 2000 m. The power must be reduced
for altitudes above 1000 m (derating). In this case, the derating is 1.5 % per 100 m.
222
6SL3700-
kg
mm
P
15
P
150
P
270
15
150
270
Duty cycle of the Central Braking Modules
1AE35-
1AE41-
0AA3
0AA3
230
230
400
400
P
15
P
P
DB
600
n
1AF35-
1AF41-
5AA3
1AA3
230
230
400
400
150
P
270
Manual, (GH5), 05/2010, A5E03263538A
1AH36-
1AH41-
3AA3
2AA3
230
230
400
400
t/s
Cabinet Modules