Bosch ICP-EZM2 System Reference Manual page 15

Easy series control panel
Hide thumbs Also See for ICP-EZM2:
Table of Contents

Advertisement

Easy Series Control Panel
Programming Item
Country Code
Enclosure Tamper Enabled
Fire Bell Cut-off Time
Intrusion Bell Cut-off Time
Intrusion Abort Window
Point Alarm Verification
Entry Delay
Auto Protection Level
Latching Point and Enclosure Tamper
Latching System Device Tamper
Restrict Installer Passcode
Start Arming With Faulted Points
Passcode Length
Circuit Style
Response Time
* The middle digits = the point number. For example, "01" = Point 1, and "32" = Point 32.
Table 1.1: NF A2P Certified Configuration Values
Notice!
For supervised points (dual EOL), 2.2k Ω EOL resistors (P/N: 47819) required.
Seal the Enclosure
1.
2.
3.
Bosch Security Systems, Inc.
Item Number
102
103
107
108
110
124
127
132
137
138
142
159
861
9xx2*
9xx5*
Open the pre-opened hole which is on the right of the enclosure.
Pass the sealing wire through this hole, and bring the two wires in the corresponding hole
of the enclosure door.
Seal the sealing lead as near as possible from the enclosure.
System Reference Guide
Agency Approvals and Requirements | en
NF A2P Approved
Range
17
1
2 or 3
2 or 3
0
0
Shorter than Exit Delay
0
1
1
1
0
6
0
4 or 5
15
Section Starting Page
System Programming
Items, page 48
User Programming Items,
page 61
Point Programming Items,
page 57
2014.09 | 01 | F.01U.306.221

Advertisement