CHAPTER 3: CONFIGURING THE D20E FIRMWARE
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Setting
Descriptions
Off Name
Specify the name of the digital output point
when it is in an off state:
• Single Point Digital Input - Off state = 0
• Double Point Digital Input - Off state = 1
The name can be entered manually, or double-
click and select from the drop-down menu.
On Name
Specify the name of the digital output point
when it is in an on state:
• Single Point Digital Input - On state = 1
• Double Point Digital Input - On state = 2
The name can be entered manually, or double-
click and select from the drop-down menu.
Control settings
Reference
Specify a text string that combines the bay
Name
name, group name, and provider name from
the General tab.
Associate
Specify the feedback digital input (typically a
Output DI or
pseudo digital input or counter) for the digital
Event
output. The associated digital input point will
change state based on the digital output state.
Trip
Specify the interlock condition for trip
Interlocking
operation on the digital output using script.
Close
Specify the interlock condition for close
Interlocking
operation on the digital output using script.
Operate
Specify the Digital Output method that applies
Method
to this DO.
The following operation methods are available:
• Direct
• Select Before Operate (SBO)
If this value is set to Direct, both the Direct and
Select Before Operate commands are
accepted by this point.
If this value is set to SBO, only the Select Before
Operate command is accepted.
Operate
Specify the maximum amount of time, in
Timeouts
milliseconds, allowed between the Select
command and Operate command.
The setting is applied when the Operate
Method is set to SBO.
Providers - Protocol settings
Reference
Specify a text string that combines the bay
Name
name, group name, and provider name from
the General tab.
Physical Index Specify the index number of a Digital Output
point. It is recommended to use one-based
increment counting.
Type
Specify the relay control type.
The relay type setting is to coincide with
hardware jumper setting in either
22: D20E-K - summary of control types
and jumper setting positions
Table 27: D20E-C - summary of control
types and jumper setting positions
99.
Activity Timer Specify the length of time (in milliseconds)
before the signal is set to inactive.
Range
ASCII
ASCII
1000 to 60000
milliseconds
Trip/Close
Form C
Table
DPSTl
Raise/Lower
on page 89, or
on page
0 to 100000 ms
GE INFORMATION
Default
10000
(10
seconds)
1, 2, ..., 8.
Trip/
Close
10 ms
71