CHAPTER 3: CONFIGURING THE D20E FIRMWARE
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Setting
Descriptions
H Limit
Specify the value for the high-value limit.
H Name
Specify the name of the high-value event.
HH Limit
Specify the value for the highest-value limit.
HH Name
Specify the name of the highest-value event.
Rate of
Specify the threshold value against which the
Change
calculated change of ratio value is compared.
Set the value to 0 in order to disable the alarm.
Note: The Rate of Change will only be applied once
the user has configured a Min and Max value for the
specific Analog Input(s), within the Calculation tab.
Rate of
Specify a name for the Rate of Change Event.
Change
If left empty, no Rate of Change Event is generated.
Name
Control settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Lower
Specify the digital output point associated with a
Control Point
lower operation applied to the analog input.
A custom window allows for the association of an
analog input to a digital output on the same device.
This feature can be disabled by leaving this setting
value empty; any lower control applied to this analog
input subtracts one from the value of this analog
input.
Raise Control
Specify the digital output point associated with a
Point
raise operation applied to the analog input.
A custom window allows for association of an analog
input to a digital output on the same device. This
feature can be disabled by leaving this setting value
empty; any raise control applied to this analog input
adds one to the value of this analog input.
Providers - Protocol settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Value Name
Specify the name of the data attribute that holds the
value (e.g., stVal, mag, etc.)
Quality
Specify the name of the data attribute that holds the
Name
quality.
Time Name
Specify the name of the attribute that holds the time
stamp.
Value Index
Read-only value for internal use.
Quality Index Read-only value for internal use.
Time index
Read-only value for internal use.
Publisher settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Point
Specify the point description of the mapped analog
Description
input.
GE INFORMATION
Range
Default
0
(disable)
67