GE Multilin D20E Installation And Maintenance Manual page 64

Ethernet i/o module
Table of Contents

Advertisement

66
Setting
Descriptions
Max Value
The function of the Max Value setting is determined
by the selection made under Transform Method:
• Scale - Specify the maximum value permitted for
this analog input. The DAP updates the database
with this value whenever the device reports that
this analog input value is greater than this
maximum. The maximum value must be set to a
value greater than or equal to the associated Min
Value setting. If no value is specified, the
maximum value checking for this analog input is
disabled.
For detailed information on the IO Scale and the
specific Provider settings, see
16: Provider- IO Scale:
• Percentage - Specify the maximum range for this
analog input. The DAP uses this value as its
maximum range (100%) during its calculation.
Percentage Example:
• Min Value = 0
• Max Value = 1000
• If percentage is at 50%, the Explore window
shows 500
Offset/Min
Specify the Offset value or the Min Raw value:
Raw Value
• The Offset value is only used when the Transform
Method is set to Scale. The Offset is used to scale
the raw value received from the device, the scaled
value is stored in the DAPserver Studio database.
• Min Raw value is only used when the Transform
Method is set to Percentage. The Min Raw value
specifies the minimum raw value for the analog
input.
Multiplier/
Specify the Multiplier value or the Max Raw value:
Max Raw
• The Multiplier value is only used when the
Value
Transform Method is set to Scale. The Multiplier is
used in conjunction with the Offset to scale the
raw value received from the device.
• The Max Raw value is only used when the
Transform Method is set to Percentage. The Max
Raw value specifies the maximum raw value for
the analog input.
Transform
Specify the method used in transforming the raw
Method
value of the analog input to the engineering value.
The available options are:
• Scale; the equation for Provider Application
Analog Input Scaling is:
Data Base Value = (Raw Value * Multiplier) + Offset
• Percentage; the equation for Provider Application
Analog Input Percentage is:
Event settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Qualification
Specify the time interval, in milliseconds, for which
Time
the AI must stay in a certain region before an event in
(ms)
generated.
LL Limit
Specify the value for the lowest-value limit.
LL Name
Specify the name for the lowest-value limit.
L Limit
Specify the value for the low-value limit.
L Name
Specify the name of the low-value limit.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Range
Table
on page 68.
Multiplier:
-10000000 to
10000000
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Default
Multiplier:
1
(disable)