Protective Earth (PE) terminal
The four power wires are circuit 1: L1N1 and circuit 2: L2N2.
1
This product has been evaluated to ±10% of the rated nominal voltage range (200–240 V) to allow for line fluctuation.
2
If the wire is more than 4.5 m (15 ft) long, HP recommends increasing the wire gauge appropriately.
3
WARNING!
Ensure that mains fault current is compatible with proper operation of the protection devices
incorporated in the equipment (5 kA rated interrupting capacity).
Example of a two-circuit connection to the building's electrical system
The certified electrician needs to configure the proper wiring based on each specific country and building
installation, ensuring that it meets the voltage, current, and power requirements specified in the above table.
NOTE:
The electrician must determine the appropriate circuit breakers, which are not shown in these schemes.
CAUTION:
Do not install the jumpers 0360-3729 in this configuration.
1.
L1 wire
2.
N1 wire
3.
L2 wire
4.
N2 wire
5.
Protective earth wire
6.
Circuit breaker L1N1
7.
Circuit breaker L2N2
8.
No jumpers (0360-3729 provided)
Circuit breakers (required)
The two customer-provided circuit breakers must meet the requirements of the printer and should be in
accordance with the Electrical Code requirements of the local jurisdiction where the equipment is installed.
If the Electrical Code requirements of the local jurisdiction require an external RCCB or GFCI for earth fault
protection, install a device with sensitivity of 100 mA or higher, with appropriate rated current for the supply
configuration. Also ensure that other protective devices for earth fault protection upstream from the printer are
always greater than the one selected for the printer.
WARNING!
Ensure that mains fault current is adequate for proper operation of the supplementary protection
incorporated in the equipment (5 kA rated interrupting capacity).
ENWW
Straight wire with ferrule to ground block
Electrical requirements
21