FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
3.
Step 6 Install a new liquid level detector and connect its cables.
Step 7 Install the air filter.
Step 8 Power on the device and tap Start on the home screen. Ensure that the smart
cooling product is running properly without any alarms.
----End
10.9 Replacing a Condensate Pump
Prerequisites
●
●
●
Before replacing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump needs to be maintained from the air return side.
Issue 01 (2022-12-30)
Remove the cable from the high liquid level detector, remove the screws from
the liquid level detector using a Phillips screwdriver, and take out the high
liquid level detector.
Figure 10-11 Removing a liquid level detector
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: flat-head screwdriver, Phillips screwdriver, socket wrench
CA UTION
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement
131