Huawei FusionCol8000-E24 User Manual page 127

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Parameter
Enable teamwork CAN
resistor
Teamwork function
Teamwork parameter
synchronization
Number of systems in
this group
Number of running
systems in this group
Issue 03 (2021-04-20)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
If Teamwork function and Teamwork parameter
synchronization are both set to Enable, you can
select Set Local or Set Teamwork when setting
parameters.
NOTE
● Set Local: Set parameters for the local unit.
● Set Teamwork: Set parameters for all units in a
teamwork group.
Specifies the total number of units in this group. The
value is an integer ranging from 1 to 32.
Specifies the number of running units in this group.
The value is an integer ranging from 1 to the value
of Number of systems in this group.
7 Power-On Commissioning
118