UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 2-1 Typical UPS configurations
Confi
gurati
on
Single
UPS
Paralle
l
syste
m
Multi-
bus
syste
m
Single UPS
The UPS uses a modular design. It uses multiple power modules connected in
parallel to deliver a high loading capacity. If one power module is faulty, other
power modules continue working. If loads are light, the UPS provides redundant
capacity even if only a single UPS is operating, which ensures high reliability.
Figure 2-1 Typical application scenario of a single UPS
Issue 03 (2021-08-03)
Application Scenario
Supplies power to common loads.
Supplies power to large-sized data centers or
important loads. It features high reliability and
strong transient overload resistance capability.
Supplies power to important loads in large- and
medium-sized equipment rooms, data centers,
and other places that require high reliability.
In addition to advantages of common parallel
systems, the multi-bus system is free from
bottleneck failures, but its configuration is
complex.
NO TE
If the mains and bypass use different power sources, ensure that the neutral wires of the
mains and bypass input power sources are equipotential. For example, the mains and
bypass inputs are from the same transformer.
Copyright © Huawei Technologies Co., Ltd.
2 Product Overview
Description
-
A maximum of four
UPSs can be
connected in
parallel.
Dual-bus supported