Startup Wizard
Q9 Plus ASD Install/Op Manual
Standard Startup Wizard
Requirements
The Startup Wizard assists the user with the initial
configuration of the Q9 Plus ASD by querying the
user for information on the ASD control settings,
motor ratings, and ASD display units. The Q9 Plus
ASD may also be setup by directly accessing each
of the settings via the Program menu or by using
the Direct Access Number of each parameter.
The Startup Wizard is launched from Program 
Utilities Standard Startup Wizard. Click Next to
continue with the Startup Wizard setup or click Exit
to reset the EOI and go to the
Screen.

Running the Startup Wizard

Input the required information into the following
screens to complete the Startup Wizard.
1. Voltage and Frequency Rating of the Motor
(
/
)
F409
F014
Motors are designed and manufactured for
operation within a specific voltage and frequency
range. The voltage and frequency specifications for
a given motor may be found on the nameplate of
the motor.
Settings:
0 — 200 v, 50 Hz
1 — 200 v/230 v, 60 Hz
2 — 380v-480v, 50/60 Hz
30
2. Upper-Limit Frequency
This parameter sets the highest frequency that the
Q9 Plus ASD will accept as a frequency command
or frequency setpoint. The Q9 Plus ASD may
output frequencies greater than the Upper-Limit
Frequency (but, less than the Maximum Frequency)
Frequency Command
when operating in the PID Control mode, Torque
Control mode, or the Vector Control modes
(sensorless or feedback).
3. Lower-Limit Frequency
This parameter sets the lowest frequency that the
Q9 Plus ASD will accept as a frequency command
or frequency setpoint. The Q9 Plus ASD will output
frequencies lower than the Lower-Limit Frequency
when accelerating to the lower limit or decelerating
to a stop. Frequencies below the Lower Limit may
also be output when operating in the PID Control
mode, Torque Control mode, or the Vector Control
modes (sensorless or feedback).
4. Automatic Accel/Decel
When enabled, the Q9 Plus ASD adjusts the
acceleration and deceleration rates according to
the applied load. The acceleration and deceleration
times range from 12.5 to 800% of the programmed
values [e.g., Acceleration Time 1 (F009) and
Deceleration Time 1 (F010) adjusted for the active
Accel/Decel times].
(
)
F012
(
)
F013
(
)
F000