IndraControl VAC 08.1 CDI+ Splitter
Fig. 10-7: RJ45 plug shielding areas
10.7.4 Additional shielding connection in case of strong electrical inter-
ferences and long cables
In case of strong electrical interferences and long cable lengths, it can be re-
quired to additionally connect the shielding to the earthing potential.
Observe the following for an additional shielding connection:
Mount suitable EMC shielding clamps close to the control cabinet PC, the re-
●
mote operator display or the CDI+ splitter
Ensure that the CDI+ cable is not crimped when connecting the shielding to
●
the equipotential bonding
Avoid mechanical stress (tensile, compressive) on the plug
●
Use an EMC shielding clamp suitable for the cable diameter. Crimping of the
●
cable impairs the electrical properties of the CDI+ cable.
To mount the shielding connection, proceed as follows:
1. Only remove the CDI+ cable jacket on the length required for the connec-
tion.
The CDI+ cable is sensitive to mechanical load where the jacket was
removed. Ensure that the CDI+ cable shielding is not damaged when
removing the cable jacket.
Fig. 10-8: CDI+ cable with RJ45 plug
Mounting, demounting and electric installation
R911400465_Edition 01 Bosch Rexroth AG
21/33