Fault
No gateway function
Multiple inexplicable effects
7KN POWERCENTER 3000 does not
establish a connection to individual
devices
Loaded project is not working
7KN POWERCENTER 3000 does
generally not work as expected
7KN POWERCENTER 3000 only communicates with known device types and known versions, i.e. only with versions xy,
1)
where x and y must be known in the 7KN Powercenter 3000. If the 7KN Powercenter 3000 has been in use for a long
time, a newly added device might have a newer, and therefore unknown, version.
See also
Firmware update (Page 113)
7KN POWERCENTER 3000
Equipment Manual, 07/2020, L1V30579222003-03
Possible measures
Modbus gateway activated at the relevant interface?
See Web user interface → Toolbar → Service overview (gearwheels), if necessary,
activate the service under Web user interface → Settings → General.
Check the device connection status in the overview of the web user interface
→ if necessary, rectify communication faults on the internal communication inter-
faces.
Check the firewall settings
Check the setup of powerconfig
→ If necessary, update and reload.
Tip: By clicking on the
the navigation bar.
Restart 7KN Powercenter 3000. See Switching the device on/off (Page 34).
Version check
could have failed
1)
→ Update 7KN Powercenter 3000.
Connect powerconfig to the relevant interface and check accessibility.
Check the network settings, e.g. only one gateway should be entered.
Load a new or modified project via the web user interface.
If this does not lead to the desired result, 7KN Powercenter 3000 can be reset via
powerconfig → Device menu → Reset → Devices (without comm. addr.) and the
project deleted.
Alternatively, 7KN Powercenter 3000 can be reset via the ON/OFF pushbutton. See
Design of the devices (Page 14).
7KN Powercenter 3000 can still be accessed via the configured IP address.
Reset 7KN Powercenter 3000 via powerconfig → Device menu → Reset → Device.
The project and all communication parameters are deleted.
Alternatively, 7KN Powercenter 3000 can be reset via the ON/OFF pushbutton.
See Design of the devices (Page 14).
7KN Powercenter 3000 can no longer be accessed via communication. First commis-
sioning must be performed again. See First commissioning (Page 45).
symbol, you can display the IP addresses of the devices on
Service and maintenance
7.2 Fault rectification