Siemens Sinamics S120 Comissioning Manual page 106

With startdrive
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Commissioning
4.5 Commissioning a drive
Calling the control panel
1. In the project navigation, select menu "Drive device_x > Drive axis_x > Commissioning".
2. In the commissioning secondary navigation, select the "Control panel" menu.
If there is no online connection, Startdrive attempts to establish a connection.
When an online connection has been established, the bar in the header area is shown in
color. The control elements are grayed-out apart from the "Activate" button. The
remaining controls only become active after you have activated the drive control panel
and set the appropriate enable signals.
Figure 4-44
Activating the drive control panel
If you activate the drive control panel, then you fetch the master control for the drive. The
drive control panel can only be activated for one drive.
Proceed as follows to activate the drive control panel:
1. Click the "Activate" button at "Master control".
The "Activate master control" message window opens.
2. Read the warning carefully and check the value for the monitoring time.
The monitoring time specifies the time during which the connection from the PG/PC to the
drive is monitored. The minimum value is 1000 ms.
3. Click the "Continue" button to confirm the monitoring time.
The message window closes. The drive control panel is then active.
106
Drive control panel
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Commissioning with Startdrive