FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Maintenance area
ECC800e
Issue 07 (2019-12-20)
Item
AC input
Operating
environment
Monitoring module
indicator
Network interface
indicator
Monitor interface
(network
management system
or Web)
Copyright © Huawei Technologies Co., Ltd.
Operation
N/A
N/A
N/A
N/A
N/A
Expected
Troubleshooting
Result
Input voltage:
If the input voltage
100–240 V AC
is abnormal, check
the power grid and
Frequency: 50
input cable
Hz/60 Hz
connection.
Ambient
If the humidity or
temperature:
temperature is
–20° C to
abnormal, check the
+65° C
smart cooling
product status.
Humidity:
5–95% RH
(non-condensi
ng)
The monitoring
If the indicator is off
module indicator
or any abnormal
is steady green or
condition occurs,
blinking green.
see
Troubleshooting the
Monitoring System
to rectify the fault.
The green
Check the network
indicator is
cable connection.
steady on, and
the yellow
indicator is
blinking.
Export smart
If an alarm is
cooling product
generated by
logs, alarms,
referring to Alarm
temperature,
References or
humidity, as well
contact Huawei
as the operating
technical support.
status and time of
the water sensor,
door status
sensor,
temperature
sensor, and
smoke sensor
from the
monitoring
system. View the
historical alarms
generated in this
quarter and select
the most
common five
ones.
4 Maintenance
4.4.2
130