FAQs

8.1

Special aspects of powerconfig 3.12

8.1.1

7KN POWERCENTER 3000 is unknown

7KN Powercenter 3000 is displayed as "unknown" in the search for available devices in
powerconfig V 3.12. The 7KN Powercenter 3000 can be identified via the displayed MAC
address (see the rating plate), the IP address, and the flashing function.
8.1.2

Inserting via library

With powerconfig V3.12, 7KN Powercenter 3000 can be inserted from the library.
7KN Powercenter 3000 can be loaded via the default IP addresses
● Internal interface X2P1: 192.168.1.2
● External interface X1P1: 192.168.0.2
or the IP address set in the search function.
The connected devices must be located both in the project and in the gateway hierarchy
under 7KN Powercenter 3000.
8.1.3

No firmware update

With powerconfig V3.12, no firmware update is offered for 7KN Powercenter 3000. The
firmware can be updated via the Web user interface. See chapter Web user interface
(Page 44).
8.1.4

Information for import and export

With powerconfig V3.12 and 7KN Powercenter 3000 V1.0, only a 7KN Powercenter 3000 pro
splx file is permissible.
8.1.5

Not all parameters are supported

Not all parameters are supported by powerconfig V3.12.
This applies in particular to the service and security settings. See Web user interface →
Settings.
7KN POWERCENTER 3000
Manual, 10/2019, L1V30579222003-01