Fundamentals

15.1

Basic information on SINAMICS S120

Reference
See also
Small SINAMICS Glossary (Page 339)
15.1.1

Rules for wiring the DRIVE-CLiQ interface

Introduction
When wiring components with DRIVE CLiQ, the following rules apply: The rules are
subdivided into obligatory rules, which must be observed, and optional rules, which enable
automatic topology detection if they are adhered to.
Obligatory rules:
● A maximum of 198 DRIVE-CLiQ node components can be connected for each NCU.
● Up to 16 nodes can be connected to a DRIVE-CLiQ socket.
● A maximum of 7 nodes can be connected in one row. A row is always considered from
● Ring wiring is not permitted.
● Components must not be double-wired.
IBN CNC: NCK, PLC, drive
Commissioning Manual, 07/2007, 6FC5397-2AP10-3BA0
the perspective of the closed-loop control module.
15
289