Parameters/address space

4.3 Declaration of parameters

4.3
Declaration of parameters
Sampling rate
Specifies the number of sub-cycles per isochronous data cycle for the for the oversampling
function.
Missing supply voltage L+
Enabling of the diagnostics, with missing or too little supply voltage L+.
Overflow
Enabling of the diagnostics if the measured value violates the high limit.
Underflow
Enabling of the diagnostics if the measured value violates the low limit.
Wire break
Enabling of the diagnostics if the module has no current flow or the current is too weak for
the measurement at the corresponding configured input or the applied voltage is too low.
Current limit for wire break diagnostics
Threshold for reporting wire breaks. The value can be set to 1.185 mA or 3.6 mA, depending
on the sensor used.
22
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 12/2016, A5E03484886-AE