Address Space - Siemens SIMATIC S7-1500 Manual

Analog input module
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Parameters/address space

4.4 Address space

4.4
Address space
The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
Configuration options of AI 8xU/I HS
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 2
Configuration options
Configuration
1 x 8-channel without value status
1 x 8-channel with value status
8 x 1-channel without value status
8 x 1-channel with value status
1 x 8-channel with value status for
module-internal shared input with
up to 4 submodules
1 x 8-channel without value status
for oversampling
Value status (Quality Information, QI)
The value status is always activated for the following module names:
● AI 8xU/I HS QI
● AI 8xU/I HS S QI
● AI 8xU/I HS MSI
An additional bit is assigned to each channel for the value status. The value status bit
indicates if the read in digital value is valid. (0 = value is incorrect).
24
Short designation/
module name in the
Integrated in hardware cata-
GSD file
AI 8xU/I HS
AI 8xU/I HS QI
AI 8xU/I HS S
AI 8xU/I HS S QI
AI 8xU/I HS MSI
---
V14 or higher with HSP 0186
Configuration software, e.g., with STEP 7 (TIA Portal)
log STEP 7 (TIA Portal)
V12 or higher
V12 or higher
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
V13 Update 3 or higher
(PROFINET IO only)
(PROFINET IO only)
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
GSD file in
STEP 7 (TIA Portal) V12 or
higher or STEP 7 V5.5 SP3
or higher
X
X
X
(PROFINET IO only)
X
(PROFINET IO only)
X
(PROFINET IO only)
---
Manual, 12/2016, A5E03484886-AE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ai 8xu/i hsSimatic et 200mp