Issue 10/06
6.4.11

Ramp function generator (RFG)

Skip frequency 1 (entered in Hz)
P1091 = ...
Defines skip frequency 1, which avoids
effects of mechanical resonance and
suppresses frequencies within +/- p1101
(skip frequency bandwidth).
Skip frequency 2
P1092 = ...
Skip frequency 3
P1093 = ...
Skip frequency 4
P1094 = ...
Skip frequency bandwidth
P1101 = ...
(entered in Hz)
Ramp-up time
P1120 = ...
(enters the accelerating time in s)
Ramp-down time
P1121 = ...
(enters the deceleration time in s)
Rump-up initial rounding time
P1130 = ...
(entered in s)
Ramp-up final rounding time
P1131 = ...
(entered in s)
Rump-down initial rounding time
P1132 = ...
(entered in s)
Ramp-down final rounding time
P1133 = ...
(entered in s)
Rounding type
P1134 = ...
0
Continuous smoothing
1
Discontinuous smoothing
OFF3 ramp-down time
P1135 = ...
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
MICROMASTER 440
Operating Instructions (Compact)
0.00 Hz
f
out
0.00 Hz
0.00 Hz
0.00 Hz
p1091
2.00 Hz
Skip frequency
10.00 s
f
p1082
(f
)
max
f
1
10.00 s
p1120
0.00 s
f
f
2
0.00 s
0.00 s
0.00 s
f
1
P1130
P1131
t
up
0
The rounding times are recommended as
abrupt responses can be avoided therefore
reducing stress and damage to the mechanical
system.
The ramp-up and ramp-down times are
extended by the component of the rounding
ramps.
6 Commissioning
p1101
Skip frequency
bandwidth
f
in
t
p1121
t
P1132
P1133
t
down
5.00 s
43