Issue 10/06
6.4.9

Fixed frequency (FF)

Fixed frequency 1
P1001 = ...
Can be directly selected via DIN1
(P0701 = 15, 16)
Fixed frequency 2
P1002 = ...
Can be directly selected via DIN2
(P0702 = 15, 16)
Fixed frequency 3
P1003 = ...
Can be directly selected via DIN3
(P0703 = 15, 16)
Fixed frequency 4
P1004 = ...
Can be directly selected via DIN4
(P0704 = 15, 16)
Fixed frequency 5
P1005 = ...
Can be directly selected via DIN5
(P0705 = 15, 16)
Fixed frequency 6
P1006 = ...
Can be directly selected via DIN6
(P0706 = 15, 16)
Fixed frequency 7
P1007 = ...
Fixed frequency 8
P1008 = ...
Fixed frequency 9
P1009 = ...
Fixed frequency 10
P1010 = ...
Fixed frequency 11
P1011 = ...
Fixed frequency 12
P1012 = ...
Fixed frequency 13
P1013 = ...
Fixed frequency 14
P1014 = ...
Fixed frequency 15
P1015 = ...
Fixed frequency code - Bit 0
P1016 = ...
Defines the selection method for fixed
frequencies.
Fixed frequency code - Bit 1
P1017 = ...
Fixed frequency code - Bit 2
P1018 = ...
Fixed frequency code - Bit 3
P1019 = ...
Fixed frequency code - Bit 4
P1025 = ...
Fixed frequency code - Bit 5
P1027 = ...
MICROMASTER 440
Operating Instructions (Compact)
0.00 Hz
5.00 Hz
10.00 Hz
When defining the function of the digital inputs
15.00 Hz
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)
In this particular mode, the appropriate
20.00 Hz
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
25.00 Hz
then these are summed. An ON command is
additionally required.
16 = Direct selection + ON command
(binary-coded + On / Off1)
30.00 Hz
In this mode, the fixed frequencies are
selected as for 15, however these are
35.00 Hz
combined with an ON command.
17 = Binary coded selection + ON command
40.00 Hz
(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective for
45.00 Hz
digital inputs 1 to 3.
50.00 Hz
55.00 Hz
60.00 Hz
65.00 Hz
65.00 Hz
1
1
Direct selection
2
Direct selection + ON command
3
Binary coded selection + ON command
NOTE
1
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
1
the drive inverter accepts the ON command.
1
1
1
Direct selection
2
Direct selection + ON command
1
6 Commissioning