Operating Instructions Fire alarm system EBL512, V2.7.x

Reset interlocking output (H9/C3)

All activated interlocking outputs are listed in this menu.
Interlocking output activated via its control expression and with
latching output not selected: The output can be reset via this menu.
Interlocking output activated via its control expression and with
latching output selected (in Win512): The output has to be reset via
this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.
Interlocking output activated via Web-server II: The output has to be
reset via this menu.
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Reset interlocking output
Reset interlocking output
area 000 point 00
Reset interlocking output
ACCEPT? H9
ACCEPT? C1
ACCEPT? C3
ACCEPT?
ACCEPT? C3
157
Comments
According to chapter
"Access", see page 92.
This is a list in which you
can scroll. If there are no
activated outputs, menu C3
will be shown again.
Press "A" (for reset) or
"Return" (no reset) to
menu C3.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.