Operating Instructions Fire alarm system EBL512, V2.7.x

Clear weekly average (H8/S5)

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
set to the default value otherwise the new / clean sensor will inherit
the old sensor's value. It is possible to clear the week average sensor
value for each sensor individually.
NOTE! First replace the sensor, then clear the week average value
as soon as possible. Authorised service personnel only, must do this.
Used incorrectly it can cause nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated
within one hour and after that each week.
Text in display
Clear weekly average
Enter technical number to clear: 000000
Clear weekly average
ACCEPT?
ACCEPT?
ACCEPT?
146
Comments
According to chapter
"Access code for
maintenance", see page
141.
S5
Write the wanted techn.
no. and/or press "A" to
accept.
Scroll or press "Return" to
S5
return to menu H8. Scroll
or press "Return" to log
off.