Fault Monitoring - Siemens SIMATIC NET SCALANCE S615 Configuration Manual

Industrial ethernet security web based management
Hide thumbs Also See for SIMATIC NET SCALANCE S615:
Table of Contents

Advertisement

Procedure
Enabling function
1. Select the "Syslog Client" check box.
2. Click the "Set Values" button.
Creating a new entry
1. In the "Server IP Address" input box, enter the IP address or the FQDN name of the
Syslog server on which the log entries will be saved.
2. Click the "Create" button. A new row is inserted in the table.
3. In the "Server Port" input box, enter the number of the UDP port of the server.
4. Click the "Set Values" button.
Note
The default setting of the server port is 514.
Changing the entry
1. Delete the entry.
2. Create a new entry.
Deleting an entry
1. Select the check box in the row to be deleted.
2. Click the "Delete" button. All selected entries are deleted and the display is refreshed.
4.4.11

Fault monitoring

Configuration of fault monitoring of status changes on connections
On this page, you configure whether or not an error message is triggered if there is a status
change on a network connection.
If connection monitoring is enabled, an error is signaled
● when there should be a link on a port and this is missing.
● or when there should not be a link on a port and a link is detected.
A fault causes the fault LED on the device to light up and, depending on the configuration,
can trigger a trap, an e-mail, or an entry in the event log table.
SCALANCE S615 Web Based Management
Configuration Manual, 05/2015, C79000-G8976-C388-02
Configuring with Web Based Management
4.4 "System" menu
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents