11.5.113 Alarm functions

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device".
11.5.114 Alarm functions — Condensate water alarm
Options:
If a fan coil is used, condensation may form during operation as a result of excessive cooling
and/or humidity. The associated condensate is typically collected in a container. To protect the
container against overflowing, and thus prevent potential damage to devices and/or the building,
the container alerts the "Condensation alarm" object (receiving only) that the maximum fill level
has been exceeded. This causes the controller to switch to a protective mode. This status is
indicated by the corresponding icon on devices that have a display. Local operation is blocked.
Operation is only possible again after the alarm has been deactivated.
Note
This parameter is only available when the "Control function" parameter is set
either on "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
11.5.115 Alarm functions — Dew point alarm
Options:
When refrigerating machines are used, dew may appear on the refrigerant supply lines during
operation as a result of excessive cooling and/or humidity. The dew indicator reports the dew
formation via the "Dew point alarm" object (receiving only). This causes the controller to switch
to a protective mode. This status is indicated by the corresponding icon on devices that have a
display. Local operation is blocked. Operation is only possible again after the alarm has been
deactivated.
Note
This parameter is only available when the "Control function" parameter is set
either on "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
Product manual 2CKA001473B9482
Description of application and parameters