3 SETUP AND USE

Table 3-5 Standard Overload Curve Trip Times (in seconds)

Overload
Level
1
1.05
853
1.10
416
1.20
198
1.30
126
1.40
91
1.50
70
1.75
42
2.00
29
2.25
21
2.50
16
2.75
13
3.00
10
3.50
7
4.00
5
4.50
4
5.00
3
5.50
2
6.00
2
6.50
2
7.00
1
7.50
1
8.00
1
*
Factory preset value
MULTILIN STANDARD CURVE NUMBERS
2
3
1707
2560
3414
833
1250
1666
397
596
795
253
380
507
182
273
364
140
210
280
84
127
169
58
87
116
43
64
86
33
50
66
26
39
53
21
32
43
15
23
31
11
17
23
9
13
18
7
10
14
5
8
11
5
7
10
4
6
3
5
3
4
2
4
66
g
*
4
5
6
5975
7682
2916
3750
1392
1789
887
1141
638
820
490
630
297
381
204
262
150
193
116
150
93
119
76
98
54
69
40
52
31
40
25
32
20
26
17
22
8
14
19
7
12
16
6
11
14
5
9
12
GE Power Management
7
8
10243
12804
5000
6250
2386
2982
1521
1902
1093
1367
840
1050
509
636
350
437
258
323
200
250
159
199
131
164
93
116
69
87
54
68
43
54
35
44
30
37
25
31
21
27
19
23
16
20