GE 169 Instruction Manual page 61

Motor management relay
Table of Contents

Advertisement

3 SETUP AND USE
3$*(
'(6&5,37,21
5
SPARE INPUT ALARM
TIME DELAY = XXX SEC.
(model 169 Plus only) This setpoint is used to set the time delay for the Spare Input Alarm:
1-254 (increments of 1) or OFF - time delay in seconds (OFF disables this function)
Factory Value = OFF
5
SPARE INPUT TRIP
TIME DELAY = XXX SEC.
(model 169 Plus only) This setpoint is used to set the time delay for the operation of the Spare Input Trip
function:
1-254 (increments of 1) or OFF - time delay in seconds (OFF disables this function)
Factory Value = OFF
5
ENABLE AUTO-RESET OF
START TRIPS ? XXX
This setpoint is used to automatically reset either STARTS/HOUR or START INHIBIT trips when
conditions permit.
YES – relay automatically resets after the STARTS/HOUR or START INHIBIT lockout time has run out.;
NO - relay must be manually reset after the STARTS/HOUR or START INHIBIT lockout time has run out.
Factory Value = NO
5
FLC THERMAL CAPACITY
REDUCTION = XX PERCENT
This setpoint is used to set the level to which the thermal memory will discharge to when the motor is
running at full load current. This level may be set as the percentage difference of the hot motor thermal
damage curve to the cold motor thermal damage curve.
Range: 5% - 50% increments of 1%; Factory Value = 15%
5
SERIAL = MASTER ? XXX
(No Indicates Slave)
(model 169 Plus only) This setpoint is used to select the relay as either a MASTER or a SLAVE for
connection in a serial communication link. When a relay is configured as a MASTER it cannot be used
for motor protection (see section 2.18):
YES - relay is configured as a MASTER; NO - relay is configured as a SLAVE. Factory Value = NO
Note: If this setpoint is changed to YES and phase currents are injected relay failure will occur.
5
SLAVE ADDRESS = XXX
Seen only when relay is chosen as a SLAVE (model 169 Plus only). This setpoint is used to set the
address of the relay to distinguish it from other devices in a serial communication link (see section 2.18):
1-254 or OFF - relay SLAVE address (OFF indicates no address). Factory Value = OFF
g
55
GE Power Management