GE 169 Instruction Manual page 49

Motor management relay
Table of Contents

Advertisement

3 SETUP AND USE
3$*(
,1)250$7,21 /,1(
1
G/F TRIP TIME DELAY
G/F DELAY= XX.X SECONDS
1
UNDERCURRENT ALARM LEVEL
U/C ALARM= XXXX AMPS
1
UNDERCURRENT TIME DELAY
U/C DELAY= XXX SECONDS
1
RAPID TRIP / MECH. JAM
TRIP LEVEL= X.X X FLC
1
RAPID TRIP TIME DELAY
DELAY= XXX.X SECONDS
1
SHORT CIRCUIT TRIP LEVEL
S/C TRIP= XX X FLC
1
SHORT CIRCUIT TIME DELAY
S/C DELAY= XX.X SECONDS
1
IMMEDIATE OVERLOAD
LEVEL = X.XX X FLC
1
END OF PAGE ONE
SETPOINT VALUES
5$1*(
0.0 (Instantaneous) – 20.0 seconds (increments
of 0.5). Additional time delay of 0.25 seconds
following 20.0.
1-1000 amps or OFF (increments of 1)
1-255 seconds (increments of 1)
1.5xFLC-4.5xFLC or OFF (steps of 0.5xFLC)
0.5-125.0 seconds (increments of 0.5)
4xFLC-12xFLC or OFF (increments of 1xFLC)
Instantaneous or 0.5-20.5 sec. (steps of 0.5)
1.01xFLC-1.50xFLC or OFF (steps of 0.01xFLC)
43
g
GE Power Management
0$18$/ 5()
3.11
3.12
3.12
3.13
3.13
3.14
3.14
3.15