USING THE IEC 61850 CONFIGURATOR
4-44
4.1.
Open Virtual input commands on relay 228.
4.2.
Open the Remote Input Status under Actual Values on Relay 254, and note
that when Virtual Input 1 of relay 228 is forced to a logic 1 or a logic 0, the
status of Remote Input 1 of relay 254 changes to the same state, proving that
the GOOSE transmission and reception were configured correctly.
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 4: 3 SERIES IEC61850 GOOSE