CHAPTER 4: 3 SERIES IEC61850 GOOSE
NOTE:
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
1.9.
Repeat for the second 3 Series relay.
1.10. Select OK to save the settings and return to the Main Menu.
- Before we can configure the relay using the IEC61850 Device Configuration tool we
must set the GOOSE message transmission of both relays to Advanced as follows:
1.11. For relay 228, open Setpoints > Communications > GOOSE Configuration >
General Settings.
For EnerVista 3 Series Setup software version 2.2x and earlier, this menu option is under
Transmission instead of General Settings.
1.12. Set the GOOSE Type to Advanced.
1.13. Select Save.
USING THE IEC 61850 CONFIGURATOR
4-35