11.6 Pneumatic connections
Input/Output
Threaded holes
Compressed air output
Range
Air capacity
Output function
Shut-off values
11.7 Air supply
1)
Instrument air
Purity:
max. particle size
Purity:
max. particle density
Oil contents:
max. concentration
Pressure dew point
Supply pressure
Air consumption
1) free of oil, water and dust acc. to DIN / ISO 8573-1
Pollution and oil content according to Class 3
2) Independent of supply pressure
11.8 Accessories
11.8.1 Mounting material
— Attachment kit for linear actuators to DIN/IEC 534/NAMUR
— Attachment kit for rotary actuators to VDI/VDE 3845
— Attachment kit for integral mounting to control valves
— Attachment kit for actuator-specific mounting to control
valves
11.8.2 Pressure gauge block (optional)
— With pressure gauges for supply and output pressure.
Pressure gauges with housing ø 28 mm (1.10 in), with
connection block in aluminum, black
11.8.3 PC adapter for communication
USB-HART modem for HART communication (see data sheet
63-6.71)
G 1/4
1/4-18 NPT
0 ... 10 bar (0 ... 145 psi)
3
> 7 kg/h = 5.5 Nm
/h = 3.2 sfcm at
1.4 bar (20 psi) supply air pressure
3
> 50 kg/h = 40 Nm
/h = 23 sfcm at 10 bar
(145 psi) supply air pressure
For single or double-acting actuators
Air is vented from actuator or actuator is
blocked in case of (electrical) power failure
End position 0 % = 0 ... 45 %
End position 100 % = 55 ... 100 %
5 μm
3
5 mg/m
3
1 mg/m
10 K below operating temperature
1.4 ... 10 bar (20 ... 145 psi)
2)
< 0.03 kg/h/0.015 scfm
11.8.4 PC software for remote configuration and
operation
DAT200 Asset Vision Basic with DTM for EDP300 (see data
sheet DS/DTM/DAT200)
11.9 Housing
Material/Ingress protection
Aluminum
Ingress protection
Surface/color (aluminum housing only)
Dipping varnish
Housing varnished black
Weight
Aluminum
Stainless steel 1.4404
(316L)
11.9.1 Mounting orientation
Any
11.10 Transmission data and influences
Output Y1
Increasing setpoint signal
Decreasing setpoint signal
Action (setpoint signal)
Increasing setpoint
Decreasing setpoint
Characteristic curve (travel = f {setpoint signal})
Linear
Deviation
Configurable zone
Configurable dead zone
Resolution (A/D conversion)
Sample rate
Ambient temperature
influence
Influence of vibration
1) Freely configurable with 20 reference points
Optional stainless steel 1.4404 (316L)
IP 65, NEMA 4X
With epoxy resin, stove-hardened
RAL 9005
RAL 9002
2.4 kg (5.29 lb)
5.5 kg (12.13 lb)
0 ... 100 %
Increasing pressure at output
0 ... 100 %
Decreasing pressure at output
4 ... 20 mA
= actuator position 0 ... 100 %
20 ... 4 mA
= actuator position 0 ... 100 %
Equal percentage 1:25 or 1:50 or 25:1 or
1)
50:1
< 0.5 %
0 ... 100 %,
0,1 ... 10 %,
> 16,000 steps
20 ms
< 0.5% for each 10 K
< 1 % to 10 g and 80 Hz
PositionMaster EDP300 | OI/EDP300-EN 53