11 Technical Data
11.1 Inputs
Two-wire technology
Nominal range
Limit values
Start
Load voltage at 20 mA
Impedance at 20 mA
Digital input
Nominal range
Control voltage
Current
Universal input
Nominal range
Load voltage at 20 mA
Impedance at 20 mA
11.2 Outputs
Digital output (control circuit to DIN 19234/NAMUR)
Supply voltage
Switching state logical
Effective direction
(configurable)
Alarm output
Nominal range
11.3 Cable connections
Electrical connections
4 ... 20 mA input
Options
Cable entry
52 OI/EDP300-EN | PositionMaster EDP300
4 ... 20 mA
Max.: 50 mA (overload)
Min.: 3.6 mA
3.8 mA
9.7 V
485 Ω
4 ... 20 mA
0 ... 5 V DC (switching state logical "0")
11 ... 30 V DC (switching state logical "2")
max. 4 mA
4 ... 20 mA
9.7 V
485 Ω
5 ... 11 V DC
„0": Current > 0.35 mA ... < 1.2 mA
„1": Current > 2.1 mA
normally logical "0" or logical "1"
4 ... 20 mA
2
Screw terminals max. 2.5 mm
2
Screw terminals max. 1.0 mm
2 threaded bores 1/2-14 NPT/M20 x 1.5
(cable gland/pipe plug optional)
cross section
Rigid/flexible wires
Flexible with wire end
sleeve
Flexible with wire end
sleeve without plastic sleeve
Flexible with wire end
sleeve with plastic sleeve
Multi-wire connection capacity (2 wires of the same cross section)
Rigid/flexible wires
Flexible with wire end
sleeve no plastic sleeve
Flexible with wire end
sleeve with plastic sleeve
11.4 Options
cross section
Rigid/flexible wires
Flexible with wire end
sleeve no plastic sleeve
Flexible with wire end
sleeve with plastic sleeve
Multi-wire connection capacity (2 wires of the same cross section)
Rigid/flexible wires
Flexible with wire end
sleeve no plastic sleeve
Flexible with wire end
sleeve with plastic sleeve
11.5 Travel
Rotation angle
Used range
(AWG 14)
Travel limit
(AWG 18)
Travel time prolongation
Dead band time limit
2
0.14 ... 2.5 mm
(AWG 26 ... AWG 14)
2
0.25 ... 2.5 mm
(AWG 23 ... AWG 14)
2
0.25 ... 1.5 mm
(AWG 23 ... AWG 17)
2
0.14 ... 0.75 mm
(AWG 26 ... AWG 20)
2
0.14 ... 0.75 mm
(AWG 26 ... AWG 20)
2
0.25 ... 0.75 mm
(AWG 23 ... AWG 20)
2
0.5 ... 1.5 mm
(AWG 21 ... AWG 17)
2
0.14 ... 1.5 mm
(AWG 26 ... AWG 17)
2
0.25 ... 1.5 mm
(AWG 23 ... AWG 17)
2
0.25 ... 1.5 mm
(AWG 23 ... AWG 17)
2
0.14 ... 0.75 mm
(AWG 26 ... AWG 20)
2
0.25 ... 0.5 mm
(AWG 23 ... AWG 22)
2
0.5 ... 1 mm
(AWG 21 ... AWG 18)
25 ... 270° for rotary actuator
25 ... 60° for linear actuator
Min. and max. limits, freely configurable in
range 0 ... 100 %
of total travel (min. range > 20 %)
Range of 0 ... 200 seconds, separately for
each direction
Setting range 0 ... 200 seconds
(monitoring parameter for control until the
deviation reaches the dead band)