GE C70 Instruction Manual page 298

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
5
Up to three identical neutral current unbalance elements, one per each installed CT/VT module.
5-174
NTRL CUR UNBALCE 1
MESSAGE
K MAG: 0.0000
NTRL CUR UNBALCE 1
MESSAGE
K ANG: 0°
NTRL CUR UNBALCE 1
MESSAGE
STG 1 PKP: 0.020 pu
NTRL CUR UNBALCE 1
MESSAGE
STG 1 SLOPE: 2.0%
NTRL CUR UNBALCE 1
MESSAGE
STG 2 PKP: 0.030 pu
NTRL CUR UNBALCE 1
MESSAGE
STG 2 SLOPE: 2.0%
NTRL CUR UNBALCE 1
MESSAGE
STG 3 PKP: 0.040 pu
NTRL CUR UNBALCE 1
MESSAGE
STG 3 SLOPE: 2.0%
NTRL CUR UNBALCE 1
MESSAGE
STG 4 PKP: 0.050 pu
NTRL CUR UNBALCE 1
MESSAGE
STG 4 SLOPE: 5.0%
NTRL CUR UNBALCE 1
MESSAGE
STG 1 DEL: 30.00 s
NTRL CUR UNBALCE 1
MESSAGE
STG 2 DEL: 10.00 s
NTRL CUR UNBALCE 1
MESSAGE
STG 3 DEL:
NTRL CUR UNBALCE 1
MESSAGE
STG 4 DEL:
NTRL CUR UNBALCE 1
MESSAGE
DPO DELAY: 0.25 s
NTRL CUR 1 BLK STG1:
MESSAGE
Off
NTRL CUR 1 BLK STG2:
MESSAGE
Off
NTRL CUR 1 BLK STG3:
MESSAGE
Off
NTRL CUR 1 BLK STG4:
MESSAGE
Off
NTRL CUR UNBALCE 1
MESSAGE
TARGET: Self-Reset
NTRL CUR UNBALCE 1
MESSAGE
EVENTS: Disabled
C70 Capacitor Bank Protection and Control System
Range: 0.0000 to 0.1500 in steps of 0.0001
Range: 0 to 359° in steps of 1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.20 s
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents