Siemens SIMATIC S7-1500 System Manual page 232

Automation system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Test functions and fault res olution
14.2 Reading out/saving service data
5. Make sure that the SIMATIC memory card is not write-protected and insert it in the slot on
the CPU.
(for the CPU 1517(F)-3 PN/DP, CPU 1517T(F)-3 PN/DP, CPU 1518(F)-4 PN/DP and
CPU 1518(F)-4 PN/DP ODK, you need a card ≥ 2 GB, and for the CPU 1511(F)-1 PN,
CPU 1511C-1 PN, CPU 1511T-1 PN, CPU 1512C-1 PN, CPU 1513(F)-1 PN,
CPU 1515(F)-2 PN, CPU 1515T-2 PN and CPU 1516(F)-3 PN/DP, a card ≥ 32 MB)
Result: The CPU writes the service data file DUMP.S7S to the SIMATIC memory card and
remains in STOP mode.
The transfer of the service data has been completed as soon as the STOP LED stops
flashing and lights up continuously. If the transfer was successful, only the STOP LED lights
up. If the transfer was not successful, the STOP LED lights up and the ERROR LED flashes.
In case of an error, the CPU stores a text file with a note on the error that occurred in the
DUMP.S7S folder.
232
Automation system
System Manual, 09/2016, A5E03461182-AD