6.
6.1.
6.2.
48
COM600 series, version 4.1
User's Manual

Configuration

Opening a project in Station Automation Builder 600

This section describes the configuration tasks common to all OPC servers, and gives an
overview of the configuration tasks related to OPC clients.
All the possible configuration scenarios are not included in
this manual. Refer to the corresponding user's manuals listed
in 1.10, Related documents for more detailed instructions.

Configuration and maintenance

SAB600 is used to configure and maintain COM600. Communication networks are
described in the Communication structure of the Project Explorer window. The structure
is built using OPC server/client, communication channel/subnetwork, and device objects.
These objects have communication properties that can be accessed via the Object Prop-
erties window. The properties define for example the communication port, bit rate, timing
parameters, unit addresses, and so on .
The substation structure of SAB600 is used to configure the HMI functions of the
COM600 products. The substation structure presents the functional view of the substation.
It includes substation, voltage level, bay, busbar, and conducting equipment objects.
The Single line diagram is a graphical presentation of the process objects in the substation.
The Single line diagram can be edited on different levels. The bay layout can be con-
figured by opening the SLD Editor from a bay object. When the SLD Editor is opened
from a voltage level object, it is possible to assign the positions of the bays within a
voltage level. The position of the voltage levels in the complete substation single line
diagram is done by opening the SLD editor from the substation object.
Substation objects are linked to communication structure objects by using the Data
Connection tool. For example, the circuit breaker object in the substation structure is
linked to the CSWI logical node in the communication structure. The link between the
structures is also used on the event list, to present the events using the names according
the substation structure.
Process data accessible on the devices is modeled according to the IEC 61850 standard.
In the communication structure this is seen as logical devices (LD), logical nodes (LN)
and data objects (DO). It is possible to insert an empty device into the structure and then
manually add and configure LD, LN, and DO objects. It is also possible to use pre-con-
figured object types of the devices, which have the objects defined and configured to
add efficiency. The device configuration can also be imported from an IED SCL
1MRS756125