32
COM600 series, version 4.1
User's Manual
Description
Conducted radio frequency
disturbance
Power frequency (50 Hz) mag-
netic field
Voltage dips and short interrup-
tions
Emission tests
Table 4.1-11 Environmental conditions
Description
Operating temperature range
Relative humidity range, non-
condensing
Storage temperature
1) Without any option cards
2) With Ethernet option card: 0...+55°C, with Serial option card: 0...+55°C, with LON option card:
0...+70°C
Table 4.1-12 Environmental tests
Description
Dry heat test
Cold test
Damp heat test, cyclic
Standard
According to IEC 61000-4-6 and IEC 60255-22-6
10 V (80% ampl. mod.)
f= 150 kHz...80 MHz
According to IEC 61000-4-8, 300 A/m, continuous
According to IEC 61000-4-11
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
According to EN 55011, and IEC60255-25, class A
Value
-25...+70ºC
1) 2)
5...95% at +40ºC
-40...+70ºC
Standard
According to IEC 60068-2-2
Test values:
96 h at +55ºC
4 h at +70ºC
According to IEC 60068-2-1
Test values:
96 h at -10ºC
4 h at -25ºC
According to IEC 60068-2-30
Test values:
6 cycles (12+12h) at +25...55°C, humidity >93%