r0303[0...n]

Motor with DRIVE-CLiQ status word / Motor w DQ ZSW

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
-
Description:
Displays the status word of the automatic motor parameter sensing of a motor with DRIVE-CLiQ.
Motor parameter sensing takes place in the following events if the SMI is connected to the Motor Module and the
encoder is activated (p0145):
- Warm restart
- downloading projects.
- POWER ON (off/on).
- where p0300 = 10000, 10001.
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: p0145, p0300
Note:
SMI: SINAMICS Sensor Module Integrated
p0304[0...n]

Rated motor voltage / Mot U_rated

VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0 [Vrms]
Description:
Sets the rated motor voltage (rating plate).
Dependency:
Refer to: p0349
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
p0305[0...n]

Rated motor current / Mot I_rated

VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.00 [Arms]
Description:
Sets the rated motor current (rating plate).
Dependency:
Refer to: p0349
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
If the rated motor current exceeds twice the maximum drive converter current (r0209), then the maximum current is
reduced due to the current harmonics that increase overproportionally (r0067).
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Motor data set selected
Motor connection type
Windings can be changed
Windings can be changed number
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
-
1 signal
MDS1
Delta
Yes
2
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
20000 [Vrms]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
10000.00 [Arms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
MDS0
Star
No
0
Access level: 1
Func. diagram: 6301, 6724
Unit selection: -
Expert list: 1
Factory setting
0 [Vrms]
Access level: 1
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
FP
-
-
-
-
121