5.6.3.3 Setting the motor rated current : C2.03
Parameter
Name
Unit
No.
Rated Output
C2.03
0.1A
Current
• C2.03 is used to set the rated current (A) shown on the motor
nameplate.
• Default value depends on the inverter capacity.
5.6.3.4 Motor no-load current : C2.04
Parameter
Name
Unit
No.
No Load
C2.04
0.1A
Current
• C2.04 is used as a reference value for the torque compensation.
• Default value depends on the inverter capacity.
• If rated voltage and rated frequency are not printed on the motor
nameplate, contact the motor manufacturer.
5.6.3.5 Setting the motor rated slip : C2.05
Parameter
Name
Unit
No.
C2.05
Rated Slip
0.01Hz
• C2.05 is used as a reference value for the torque compensation.
• Default value depends on the inverter capacity.
• Calculate C2.05 from the value printed on the motor nameplate:
Rated slip=rated frequency(Hz) - rated speed(r/min) × number of
5. Parameters
5-39
Changeable
Setting
Factory
during
range
Setting
operation
0.0
*
X
~999.9
Changeable
Setting
Factory
during
range
Setting
operation
0.0
*
X
~999.9
Changeable
Setting
Factory
during
range
Setting
operation
0.00
*
X
~600.0
poles/120
MOSCON-E7 User's Manual
5-40
5.6.4 H/W Adjusting data : C3.01~C3.06
Parameter
Name
Unit
No.
DC Voltage
C3.01
-
Compensation
Analog Output
C3.02
Compensation
-
Coefficient
Current Detector
C3.03
Compensation
-
Coefficient 1
Current Detector
C3.04
-
Compensation
Coefficient 2
Analog Command
C3.05
-
Compensation
Coefficient
Current Terminal
C3.06
Gain Compensation
-
Coefficient
Current Detector
C3.07
Compensation
-
Coefficient
CAUTION
!
• C3.01~C.07 are set from the factory and the user is not allowed to
change the setting. (Modification may influence to system
performance)
Changeable
Setting
Factory
during
range
Setting
operation
-
*
X
-
*
X
-
*
X
-
*
X
-
*
X
-
*
X
-
*
X