en | System Configuration
4.7

Controlling Outputs

In the Output Control menu you can activate and deactivate the
individual outputs for test purposes. When you exit operating
level 3, all activations of the outputs are reset to the normal
state again.
4.7.1

Notification appliance 1

7
1
ACK
4.7.2
Notification appliance 2
7
2
ACK
2014.06 | 7.0 | F.01U.172.980
Press zone key 7.
This takes you to the Output Control menu.
Press zone key 1.
This takes you to the NAC 1 submenu.
Press the ACK key.
RESET
Notification appliance 1 is activated.
Press the RESET key.
Notification appliance 1 is deactivated.
Press zone key 7.
This takes you to the Output Control menu.
Press zone key 2.
This takes you to the NAC 2 submenu.
Press the ACK key.
RESET
Notification appliance 2 is activated.
Press the RESET key.
Notification appliance 2 is deactivated.