3. Mounting to the control panel

3.1 Site selection

This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable or explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into contact
with the controller
3.2 External dimensions (Unit: mm)
48
(Fig. 3.2-1)
3.3 Panel cutout (Unit: mm)
(Fig. 3.3-1)

3.4 Mounting

Mount the controller vertically so that dust and water do not enter, fulfilling the Dust-proof/Drip-proof
specification (IP66).
Mountable panel thickness: 1 to 10mm
(1) Insert the controller from the front side of the panel. (Fig. 3.4-1)
(2) Insert the mounting frame until 2 tips of the frame touch the panel. (Fig. 3.4-2)
(3) Tighten screws with 3/4 rotations upon the screw tips touching the panel.
(Fig.3.4-1)
, Pollution degree 2
98.5
10.6
101 (*)
(32 to 122 )
(*): When terminal cover is added
6
(Fig.3.4-2)