6.2 Sub setting mode

To go to the Sub setting mode, press the
Set each setting item with the
Display
key while holding down the
or
key, and register the value with the
Item, Function, Setting range
AT (Auto-tuning) selection
• Selects auto-tuning Perform/Cancel.
Not available for program control standby status and for
control actions other than PID action.
: AT Cancel
OUT1 (Heating) proportional band setting
• Sets the proportional band for OUT1 (Heating side).
• ON/OFF action when set to 0.0.
• Setting range: 0.0 to 110.0% [Percentage of the scaling span
(scaling high limit-scaling low limit)]
OUT2 (Cooling) proportional band setting
• Sets the proportional band for OUT2 (cooling side).
• ON/OFF action when set to 0.0.
• Not available if Heating/Cooling control option is not added or
if OUT1 (Heating side) is ON/OFF action
• Setting range: 0.0 to 10.0 times OUT1 (Heating) proportional band
OUT1 (Heating) integral time setting
• Sets the integral time.
• Setting the value to 0 disables the function. (PD action)
• Not available if OUT1 (Heating) is ON/OFF action
• Setting range: 0 to 1000 seconds
OUT1 (Heating) derivative time setting
• Sets the derivative time.
• Setting the value to 0 disables the function. (PI action)
• Not available if OUT1 (Heating) is ON/OFF action
• Setting range: 0 to 300 seconds
ARW setting
• Sets the ARW (anti-reset windup).
• Available only for PID action.
• Setting range: 0 to 100%
OUT1 (Heating) proportional cycle setting
• Sets OUT1 (Heating) proportional cycle.
• Sets the proportional cycle.
• Not available for DC current output type or
if OUT1 (Heating) is ON/OFF action.
• Setting range: 1 to 120 seconds
OUT2 (Cooling) proportional cycle setting
• Sets OUT2 (Cooling) proportional cycle.
• Not available if Heating/Cooling control option is not added or
if cooling output is ON/OFF action.
• Setting range: 1 to 120 seconds
Manual reset setting
• Sets reset value manually.
• Available only for P or PD action.
Proportional band converted value (For DC input, the
placement of the decimal point follows the selection.)
A1 value setting
• Sets A1 action point. Setting the value to 0 or 0.0 disables the
function (except process high alarm and process low alarm).
• Not available if No alarm action, Timer function or Pattern end
output is selected during A1 type selection
• Setting range: See (Table 6.2-1).
A2 value setting
• Sets A2 action point. Setting the value to 0 or 0.0 disables the
function (except process high alarm and process low alarm).
• Not available if No alarm action, Timer function or Pattern end
output is selected during A2 type selection
• Setting range: See (Table 6.2-1).
16
key in the PV/SV display mode.
key.
Default value
AT Cancel
: AT Perform
2.5%
1.0 times
200 seconds
50 seconds
50%
Relay contact: 30sec
Non-contact
voltage: 3sec
DC current: Not
available
30 seconds
0.0
0
0