11.1

Terminal Blocks, Terminal Bus, and Power Cables

Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and
circuit protection device requirements.
The terminal blocks for the 100/150 kVA UpS are shown in Figure 11.2. The terminal blocks are located
inside, at the bottom of the UpS.
external cable size, lug, and tightening torque recommendations are listed in Table 11.1 – 11.2.
Use only copper wires for external cables.
1
2
3
U
V
w
AC InpUT
Some 100/150 kVA units are equipped with terminal bus strips in place of terminal blocks. Terminal bus
details are shown in Figure 11.3.
30
4
5
6
U
V
w
bypASS InpUT
FIGURE 11.2 - TERMINAL BUS FOR 100/150 KVA UPS UNITS
5.3 in. (135 mm)
1.75 in.
(45 mm)
3 in.
(77 mm)
FIGURE 11.3 - TERMINAL BUS DETAIL
G8000 Series with Isolated output Installation and operation manual
7
8
9
10
U
V
w
n
AC oUTpUT
1.97 in.
1.77 in.
(50 mm)
(45 mm)
11 12
13
+
AlT
bATTery