Chapter 2
Table 2-6. 230/240 VAC PDU Power and Current
Component
(Note 1, 2)
230/240 VAC
PDU
HP NetServer
LH 4r
HP NetServer
Rack Storage/12
HP NetServer
Rack Storage/8
HP Console
Switch
15-21 inch
Monitor
Note 1 More ratings are listed in Tables 3-7 (230/240 VAC). For a full list of power
ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web
Site.
Note 2 Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 230/240 VAC Configuration
Figure
10 shows a UPS connected to the power mains through an attached
2-
power cord (appropriate cords are supplied for each situation automatically). The
UPS has eight IEC 320 receptacles for use with the rack jumper cords. The
E7671A PDU connects to the UPS via a detachable line cord, which connects to
the PDU via a C19 plug. This cord connects to the UPS with a C20 plug. The
230/240 VAC PDU has two IEC 320, C19 and six IEC 320, C13 receptacles for
connecting rack jumper cords. The fan assembly plugs in using one of the C13
receptacles. (No fan assembly is required when perforated doors--or no doors--
are used.)
36
Connecting and Routing Cables to the HP NetServer LH 4r
Model
E7671A or E7672A
D7093A (400 MHz/512)
D7095A (400/1M)
D6970A (450 MHz/512)
D6972A (450 MHz/1M)
D5989A
D4902A
J1497A
varies
Input
Input
Current
Power
Power
(A)
(VA)
(W)
N/A
N/A
maximum
16
1120
1100
4.9
548
537
2.3
211
209
0.9
42
29
0.2
200
140
0.6