5.5

Front Panel Settings

Listed below are the default settings of the primary UPS parameters.
Settings
1) O/P VOLT SET
(output voltage
set)
2) I/P FREQ SET
(input frequency
setting)
3) I/P BYPASS
SET
(input bypass
setting)
4) FREE RUN
SET
5) HE MODE SET
6) MANUAL
BYPASS
Options
100/110/115/120/127
208/220/230/240 Vac
+/- 2%
+/- 5%
+/- 7%
+/- 10%
+10% -15%
+15% -20%
ON/OFF
ON/OFF
ON/OFF
Default
120 V
230 V
+/- 5%
+10%
-15%
ON
OFF
OFF
12
Remarks
120 V (FOR LV series)
230 V (FOR HV series)
Input Frequency range in
Free Run mode
Input Voltage range when
Bypass mode is on
If ON, enable UPS runs on
Asynchronous mode.
For example:
If input freq 55Hz
output freq stays at 60Hz.
If OFF, disable UPS runs on
synchronous mode.
For example:
If input freq 55Hz,
UPS will go to battery mode.
If ON, enable UPS runs in
High efficiency mode. The
unit will be in bypass mode
with 95% or higher
efficiency.
If OFF, the unit will be in the
online mode with 85%
efficiency.
If ON, enable UPS switch to
Bypass mode immediately.