than a second and the on-line mode can be reactivated immediately. Switching back to
online mode occurs when the input voltage exceeds ±10% (or ±15% selectable), when
the input frequency exceeds ±3Hz, or when no input line is available.
Although high efficiency is standard, the default operation is the on-line mode. From
the LCD display panel, Bypass can be activated as required or On-line operation can be
run permanently if preferred.
2.3

Free Run Mode

Free run mode is a mode of operation in which the UPS outputs a pre-set frequency (50
or 60 Hz) regardless of the input frequency. The UPS operates in free run mode when
the input frequency is outside of the selected input frequency range. When starting the
UPS, the targeted frequency is 50 or 60 Hz ±0.25 Hz.
2.4

Diagnostic Tests

When the UPS is started, a diagnostic test is executed automatically that checks the
electronics and battery, and reports any problems on the LCD display.
The advanced battery management system monitors the performance of the battery and
will indicate if battery replacement is required. The battery management system tests
the battery every 30 days of normal mode operation. A battery discharge test is
performed and reports any problems on the LCD display.
Except during the first 24 hours after startup while the UPS is in charging mode,
diagnostic tests can be performed manually from the front panel when required.
2.5

System Configuration

The UPS device and the internal backup battery make up the system. Depending on the
site and load requirements of the installation, available options may be utilized to create
a tailored solution.
Planning a UPS system should include the following considerations: