Mitsubishi Electric MXZ-SM72TAM-U1 Service Manual page 85

Hide thumbs Also See for MXZ-SM72TAM-U1:
Table of Contents

Advertisement

7105 (EF): Address setting error
Diagnosis of failure
<M-NET RC (main)>
Check whether the M-NET RC (main) address is
set in 000, or in the range of 101 to 150.
<M-NET RC (sub)>
Check whether the M-NET RC (sub) address is
set in 000, or in the range of 151 to 200.
OCH800A_85
Is the address setting correct?
Yes
Is the address setting correct?
Yes
Set the address properly, then turn the power
No
OFF of indoor/outdoor unit, Fresh Master,
Lossnay and remote controller simultaneously
for 2 minutes or more, and turn the power back
ON.
Replace the M-NET RC (main).
Set the address properly, then turn the power
No
OFF of indoor/outdoor unit, Fresh Master,
Lossnay and remote controller simultaneously
for 2 minutes or more, and turn the power back
ON.
Replace the M-NET RC (sub).
Chart 2 of 2