75BDL4003H
2.6.
Ventilation Requirements for
enclosure location
•
The operating temperature for the display is 0°C~40°C
•
Keep sufficient space for heat dispersal.
•
Consider using the cooling or heater system to maintain
the operating temperature within range.
1. Thermal Sensor:
To accurately measure the internal temperature, install
thermal sensors.
2. Fan:
Use fans to allow cool air to enter the enclosure from the
bottom and exit from the top.
3. Heater (for low temperature environment ):
Place the heater at the bottom of the enclosure.
4. Air conditioner (for high temperature environment):
Place the air conditioner at the top of the enclosure.
5. Dustproof and waterproof:
To ensure normal operation, it is recommended to design
the enclosure to meet the IP65 requirement.
16