Mounting Structure Requirements - Huawei LUNA2000-200KTL-H1 User Manual

Smart power control system
Table of Contents

Advertisement

LUNA2000-200KTL-H1 Smart Power Control System
User Manual

4.2.2 Mounting Structure Requirements

Issue 08 (2024-01-23)
sunlight, the power of the Smart PCS may decrease as the ambient
temperature increases.
If the Smart PCS has not been running for six months or longer after being
mounted, it may fail and must be checked and tested by professionals before
being put into operation.
Ensure that the installation surface is solid enough to bear the weight of the
Smart PCS (for details, see
loss caused by the collapse of the mounting structure or other reasons.
Take waterproof and insulation measures for unused DC power cables to
avoid personal injury or property loss caused by accidental contact with high
voltage or other reasons.
AC and DC power cables must be vertically routed into combiner boxes and
wiring terminals to avoid damage caused by horizontal stress on the
terminals, which is not covered under the warranty.
The Smart PCS will be corroded in salt-affected areas. Before installing the
Smart PCS outdoors in salt-affected areas, consult the Company. A salt-
affected area refers to a region within 500 m of the coast or prone to sea
breeze. Regions prone to sea breeze vary with weather conditions (such as
typhoons and monsoons) or terrains (such as dams and hills).
NO TE
● Class C environment: Outdoor areas more than 500 m away from the sea. If a site
is near a pollution source, it is 1500–3000 m away from heavy pollution sources,
such as smelteries, coal mines, and thermal power plants; 1000–2000 m away from
medium pollution sources such as chemical factories, rubber plants, and
electroplating factories; or 500–1000 m away from light pollution sources, such as
packing houses, tanneries, boiler rooms, slaughterhouses, landfill sites, and sewage
treatment plants.
● Class D environment: Sea environments or outdoor areas within 500 m away from
the sea. If a site is near a pollution source, it is within 1500 m away from heavy
pollution sources such as smelteries, coal mines, and thermal power plants; within
1000 m away from medium pollution sources such as chemical factories, rubber
plants, and electroplating factories; or within 500 m away from light pollution
sources such as packing houses, tanneries, boiler rooms, slaughterhouses, landfill
sites, and sewage treatment plants.
● Class E environment: Special environments, such as underground or underwater
environments.
The structure where the device is installed must be fireproof.
Do not install the device on flammable building materials.
The device is heavy. Ensure that the installation surface is solid enough to
bear the weight of the device.
In residential areas, do not install the device on gypsum boards or walls made
of similar materials with weak sound insulation performance to avoid
disturbing residents.
Copyright © Huawei Technologies Co., Ltd.
Figure
4-1) to avoid personal injury or property
4 Installation
29