8
GFK-2573K
Important Product Information for this Release
Upgrades
The PNC can be field-upgraded to firmware version 2.11 using the Winloader firmware upgrade kit
82A1790-MS10-000-A9, which can be downloaded from
Compatibility
The following CPU firmware, programming software and backplane hardware versions are required to use the features
introduced in PNC release 2.11 and later:
Subject
PLC CPU Firmware
Version Requirements
Programmer version
requirements
VersaMax PROFINET
Scanner
††
Attempts to store a configuration utilizing this feature to a prior-release PNC will result in an "Unable to deliver configuration to
module" fault, leaving the PNC un-configured.
New Features and Enhancements
Firmware version 2.11 adds support for the following new features:
Increased number of Profinet Devices that PNC can control from 64 to 128.
Added new "SFP OK" status bits to existing PNC status dword.
Introduced new "Critical Network Port" diagnostic fault configuration and logging.
Problems Resolved in This Release
None
Feature
RX3i PNC001 release 2.11 (or later)
Hot Standby Redundancy with PROFINET I/O
RX3i PNC001 Release 2.00
Hot Standby Redundancy with PROFINET I/O
Non Hot Standby Redundancy system
RX3i PNC001 Release 2.11 (or later)
• 128 Profinet Device Support
• "Critical Network Port"
††
RX3i PNC001 Release 2.00 (or later)
Hot Standby Redundancy with PROFINET I/O
Non Hot Standby Redundancy system using
CRU320
RX3i PNC001 Release 2.00 (or later)
Non Hot Standby Redundancy system
As a redundantly-controlled I/O Device
As a simplex I/O Device
IC695PNC001-AJ PROFINET Controller Module
http://support.ge-ip.com.
CRU320 Primary Firmware Release 8.40
CRU320 Boot Firmware Release 5.10
(Other CPU models are not supported)
CRU320 Primary Firmware Release 8.00
CRU320 Boot Firmware Release 5.10
(Other CPU models are not supported)
CPU320/CPU315 Primary Firmware Release 7.13
CPU320/CPU315 Boot Firmware Release 5.10
CPE310/CPE305 Primary Firmware Release 7.10
CPE310/CPE305 Boot Firmware Release 7.10
CRU320 Primary Firmware Release 8.00
CRU320 Boot Firmware Release 5.10
(Other CPU models are not supported)
PME 8.50 SIM 9 or 8.60 SIM 1
††
Proficy Machine Edition 8.00 SIM 5
Proficy Machine Edition 7.00 SIM 8
IC200PNS001/0 Firmware Release 2.00
IC200PNS001/002 Firmware Release 1.00